Adaptive Hysteresis Active Power Filter using Fuzzy-Logic Controller for Nonlinear Systems

Document Type : Original Article

Authors

Dept. of Industrial Electronics and Automatic Control Engineering, Faculty of Electronic Engineering, Menoufia University

Abstract

The widespread use of nonlinear loads is the main reason of lower efficiency, poor power factor, Harmonic distortion problems appear in the AC systems. In this paper, TakagiSugeno (TS) Fuzzy Logic Controller (FLC) is applied to a threephase Shunt Active Power Filter (SAPF) for improving the performance of the non linear systems. The main advantage that makes the FLCs distinguish over the other conventional controllers like Proportional Integral (PI) controller is that it does not need any mathematical model of the system. In this paper, the FLC controller is mainly used to maintain the dc-side capacitor voltage of the Voltage Source Inverter (VSI) nearly constant. Furthermore, in this paper, the adaptive hysteresis current controller (AHCC) is applied as a pulse widthmodulation (PWM) technique for switching signal generation. Simulation and experimental results are performed using MATLAB/SIMULINK, showing that the TS-FLC introduces a better dynamic behavior than the conventional (PI) controller as it has a strong robustness to the load changes and other parameters of the system.

0px; "> [1] T.Mahalekshmi,"current harmonic compensation and power factor
improvement by hybrid shunt active power filter" international journal of
computer applications (0975 8887) volume 4 no.3, July 2010.
[2] M. Palandöken. M. Aksoy. M. Tümay, "A Fuzzy-Controlled Single-Phase
Active Power Filter Operating With Fixed SwitchingFrequencyFor Reactive
Power And Current Harmonics Compensation" Electrical engineering
(2003) 86: 916doi 10.1007/s00202-003-0183-5.springer-verlag 2003
[3] H. Akagi, Y. Kanazawa and A. Nabae, Instantaneous reactive power
compensators comprising switching devices without energy storage
components, IEEE Trans. Ind. Appl., Vol. IA-20, No.3,1984,PP .625-630.
to; -webkit-text-stroke-width: 0px; ">[4] W. M. Grady, M. J. Samotyj and A. H. Noyola, Survey of active power line
conditioning methodologies, IEEE Trans. Power Del., Vol 5, No. 3, 1990,
pp. 1536-1542.
[5] F. Z. Peng, H. Akagi, and A. Nabae, “Study of active power filters using
quad series voltage source PWM converters for harmonic compensation,”
IEEE Trans. Power Electron., vol. 5, no. 1, pp. 915, Jan. 1990.,3, pp. 1536
1542, Jul. 1990.
[6] P Rathika, Dr D Devaraj," Artificial Intelligent Controller based ThreePhase Shunt Active Filter for Harmonic Reduction and Reactive Power
Compensation" proceedings of the International Multi conference of
engineers and computer scientists 2010 Vol 2,IMECS 2010,March 17-
19,2010,Hong Kong.
[7] S. Jain, P. Agarwal, and H. O. Gupta, “Design simulation and experimental
investigations on a shunt active power filter for harmonics and reactive
power compensation,” Elect. Power Common Syst, vol. 32, no.7, pp. 671–
692, Jul. 2003.
[8] Jain, S.K.; Agrawal, P.; Gupta, H.O.; , “Fuzzy logic controlled shunt active
power filter for power quality improvement, "Electric Power Applications,
IEEE Proceedings - , vol.149, no.5,pp. 317- 328, Sep 2002
[9] C. N. Bhende, S. mishra and S. k. Jain, “TS-Fuzzy controlled active power
filter for load compensation,” IEEE Transaction on Power Delivery,
vol.21,no.3, July 2006.
[10] S. K. Jain, P. Agrawal, and H. O. Gupta, “Fuzzy logic controlled shunt
active power filter for power quality improvement,” Proc. Inst. Elect Eng.,
Electr. Power Appl., vol.149, no.5, 2002.
[11] P Rathika, Dr D Devaraj," Artificial Intelligent Controller based ThreePhase Shunt Active Filter for Harmonic Reduction and Reactive Power
Compensation" proceedings of the International Multiconference of
engineers and computer scientists 2010 Vol 2,IMECS 2010,March 17-
19,2010,Hong Kong.
[12] Y. Suresh A.K. Panda and M. Suresh “Real-time implementations of
adaptive fuzzy hysteresis-band current control technique for shunt active
power filter” Vol. 5, Iss. 7, pp. 1188–1195, IET Power Electronics, 2012..
[13] S. Buso, S. Fasolo, L. Malesani, P. Mattavelli, A Dead Beat Adaptive
Hysteresis Current Control, IEEE Trans. Ind. Appl. 36 (4) (2000) 1174
1180.
[14] Anita Choudhary1 . A Study Of Hysteresis Band Current Control Scheme
For Shunt Active Power Filter Used For Harmonics Mitigation ,
(IJARCET), Volume 4 Issue 6, June 2015.
[15] L. Zelloumaa, B. Rabhib S. Saadc, A. Benaissad and M. F. Benkhorise , “
Fuzzy logic controller of five levels active power filter” IEEE Proceedings -
vol74 , pp.1015 1025 ,2015